Acceptance Test Procedure & Checklist for Marshalling Cabinets
A
marshalling cabinet is an electrical enclosure used in industrial control
systems to organize and manage wiring between field instruments and a control
system like a BMS, SCADA, PLC, DCS. It acts as a central hub for grouping
different types of inputs/outputs (I/O) and cross-wiring them, which simplifies
maintenance, improves safety, and reduces installation time.
Key functions and purpose
·
Purpose:
To
organize, protect, and terminate field wiring before connecting to the control
system's I/O cards. It simplifies the wiring process and makes maintenance and
troubleshooting easier.
·
Function
Signal
routing: Uses
"cross-wiring" to re-route signals from multi-core field cables to
the correct Input/Output (I/O) modules based on signal type (analog or digital)
and I/O assignments.
Signal
grouping: It
groups different types of signals, such as analog input, analog output, digital
input, and digital output.
Signal
conditioning: Can
contain signal isolators and conditioners to prepare signals for the control
system.
Protection: Includes safety components like relays, fuses, circuit
breakers, and surge protection.
·
Common
components
Terminal
blocks, relays, fuses, power supplies, signal isolators, wiring ducts, and
surge protection devices.
·
Signals
and voltage
Handles
various industrial process signals, such as 4–20 mA, as well as digital inputs
and outputs. The voltage can vary depending on the specific application.
·
Wiring
organization:
It
provides a clean, organized point for all the field wiring to be terminated and
connected.
·
Typical
location
Found in
industrial facilities like power plants, refineries, and chemical plants, often
situated in a control room or instrument technical room.
·
Cross-wiring:
It allows
field wiring signals to be cross-wired, meaning they are routed to the correct
terminal on the control system's I/O module, even if the physical and logical
connections are different.
·
Simplified
maintenance:
By
providing a single, organized point of contact, it makes it much easier for
maintenance personnel to identify and troubleshoot issues without having to
access the control system itself.
·
Safety:
It can
include safety features like fuses and signal isolators, which protect the
control system and personnel.
·
Flexibility
and expansion:
The organized structure makes it easier to add or change connections for future system expansions and upgrades.
The main goal of the inspection involves verifying that the marshalling cabinet satisfies project requirements as well as both industrial standards and operational performance specifications. All electrical and communication connections can operate according to design while on-site commissioning duration decreases thanks to this procedure.
Scope
of the inspection Procedure for Marshalling Cabinet
This
procedure defines inspection and testing standards for marshalling cabinets
occurring during equipment manufacturing at manufacturer’s facilities. It
includes:
·
Visual
inspection
·
Mechanical
verification
·
The
inspections involve tests for both electrical continuity and insulation
resistance.
·
Functional
testing
· Documentation verification
Inspection
Procedure – Reference Standards
·
IEC
61439 – Low Voltage Switchgear and Controlgear Assemblies
·
IEC
60204 – Safety of Machinery – Electrical Equipment
·
IEEE
Std. 1100 – Powering and Grounding Electronic Equipment
· Customer project specifications
Responsibilities
of Team Involved in Marshalling Cabinet FAT Procedure
·
The
manufacturer must fulfill technical requirements through testing capabilities
as part of their responsibilities.
·
End
users must witness the FAT procedure to check compliance of the system.
· Third-Party Inspector (if applicable): Ensures adherence to standards and specifications.
Required
Tools and Equipment for Marshalling Cabinet FAT Procedure
·
Digital
Multimeter
·
Insulation
resistance tester (Megger)
·
Earth
continuity tester
·
Function
generator (for signal simulation)
·
Power
supply (as per system voltage requirements)
·
Communication
testing tools (as applicable)
·
Standard
inspection checklist
·
Thermal
imaging camera (for heat dissipation checks)
· Users need a torque wrench to confirm proper tightening of terminals.
Step by
Step Inspection Procedure for Marshalling Cabinet
Step 1:
Visual Inspection
·
Check
that the cabinet has proper structure integrity along with correct door
alignment and appropriate ventilation openings.
·
The
project requirements must be satisfied by the selected paint and its surface
finish.
·
Confirm
that all nameplates and identification labels as well as terminal markings
remain in place.
·
All
components need to have their correct grounding and bonding connections
verified.
·
Check
that internal components match the specifications of approved drawings.
·
Verify
that installed converters contain all required signal elements including
current to voltage converters and voltage to current converters as well as
temperature signal converters.
·
Technical
team members must establish the physical existence and correct placement of
temperature transmitters alongside PLC modules together with power
supply units, interface modules and communication gateways.
·
Check
that ventilation fans remain in correct positions with working functionality.
·
Perform
a check to verify both the presence of surge protection devices and their
functional status.
· Signal wires should be clearly separated from power cables through correct wiring practices.
Step 2:
Mechanical Inspection
·
Check
that all doors and panels and locking mechanisms move with normal operation.
·
Examine
the integrity of cable entry points and gland plate components.
·
The
inspector needs to examine the equipment for components that are loose and test
for edges that are sharp or detect any problems with the assembly process.
· The system should have operational ventilation systems with effective heat dissipation mechanisms.
Step 3:
Electrical Inspection
·
The
installation of cables and wire terminations must follow established industry
protocols.
·
You
must examine terminal tightness with a torque wrench.
·
The
inspector must check whether all required ferrules and tags and cable markers
are present.
·
Inspection
must confirm that interface modules and power supplies along with converters
have their grounding connections set correctly.
·
Examine
the condition of fuses together with MCBs (Miniature Circuit Breakers) while
assessing power distribution integrity.
· Ensure power supply redundancy along with automated power failover system functionality delivers the required specifications.
Step 4:
Continuity and Insulation Resistance Tests
·
Examine
all wiring connections with the help of a multimeter during continuity tests.
·
Perform
insulation tests with a megohmmeter set to apply 500V or 1000V for control
circuits and 250V for communication circuits and 5kV for high-voltage circuits
after applicable.
·
Check
the integrity of grounding systems while measuring earth resistance values.
· Check shield continuity for signal cables.
Step 5:
Functional Testing
·
After
applying power to the cabinet you should check voltage levels throughout
different locations.
·
Test
modules and interface modules by providing simulated signals that ensure their
correct operation as well as the temperature transmitters and PLC modules.
·
Perform
validation of control communication standards which include Modbus RTU, Modbus
TCP/IP, Profibus DP, Foundation Fieldbus and Ethernet/IP and other protocols.
·
Check
alarm and trip circuits for correct functionality.
·
Conduct
verification of the system safety features by analyzing the interlocking and
fail-safe mechanisms.
·
The
system requires testing of power supply redundancy alongside interface module
and communication gateway redundancy.
·
Check
status LEDs and indicators for proper operation.
· Test the signal isolators and converters to ensure they operate correctly.
Step 6:
Communication and Signal Testing
·
Test
how signals transmitted from the marshalling cabinet reach
the control system.
·
The
function generator together with appropriate software tools must be utilized to
test analog and digital I/O signals.
·
Signal
quality tests should include proofs of accuracy as well as response time
measurements.
·
Test
the signal conversion mechanism installed in the marshalling cabinet to verify
proper operations between 4-20mA and 1-5V and RTD to 4-20mA conversion types.
· Each signal should undergo a complete loop testing procedure.
Step 7:
Power-Up and Load Test (If Required)
·
Test
the cabinet operation through simulated load conditions to check for
operational stability while power is active.
·
Thermal
imaging cameras should be used to detect cabinet temperatures that rise above
normal levels.
·
Examine
the equipment by listening for abnormal noises and inspecting for fan
vibrations or any abnormal device behavior.
·
Check
that the system operates within specified load parameters while verifying
redundancy in power supply systems.
·
Check
the power consumption rates to verify they meet design requirements.
· Throughout testing verify that each component of the cooling system operates correctly including ventilation fan functionality.
Step 8:
Final Inspection and Documentation Verification
·
An
inspector must examine test documentation and ensure that all test results
satisfy the FAT specifications.
·
Compare
as-built documentation with physical components to identify any
discrepancies that need correction.
·
All
recorded deviations should undergo documentation and require corrective
measures for necessary adjustments.
·
Field
technicians need to confirm that wiring schematics and Bill of Materials
(BOM) list match the actual installed components together with termination
drawings.
· Stakeholders who include customer representatives must provide their authorization before giving their final approval.
Step 9:
Acceptance Criteria
·
All marshalling
cabinets must fulfill their design requirements defined in the approved
drawings and specifications.
·
All
electrical wiring needs to successfully complete tests for insulation
resistance and continuity checks.
·
All
functional testing must demonstrate component functionality.
·
Physical
examination must reveal no signs of defects and installation errors together
with an absence of damages.
·
The
complete operation of signal converters along with interface modules and
temperature transmitters should be ensured.
· All technical documentation needs to remain complete and precise alongside its regular updating.
Step
10: Test Report and Sign-Off
A
comprehensive FAT Completion Report must be generated with documentation
signatures at end of successful FAT evaluation. including:
·
Inspection
checklists
·
Test
data and results
·
Photographic
evidence (if required)
·
The
document contains all nonconforming items together with their corrective
measures.
·
Measuring
instruments which participated in the FAT should have their calibration
certificates available.
·
Signatures
from responsible parties (Manufacturer, Customer, Inspector)
Common Mistakes in Factory Acceptance Tests (FAT) and Site Loop Checking
The
successful execution of a FAT minimizes system problems during commissioning
thus enabling a seamless site installation process. The stakeholders need to
perform thorough inspections and tests on the marshalling cabinet to confirm
its reliability and functionality prior to deployment.
Multiple
common errors occur during Factory Acceptance Tests (FAT) and site loop
checking activities such that they trigger delays and system errors and
malfunctions. The following list includes frequent mistakes identified during
activities and FAT and site loop checks.
1. Incorrect Cable Selection: Use of the
wrong type of multi-pair/multi-core cables (e.g., individual shield vs. overall
shield).
2. The terminal points contain improper
wire connections which lead to loose wiring.
3. The incorrect application of ferrules,
lugs and terminations leads to improper Lugging and Termination.
4. Incorrect Cable Glands: Improper
selection or installation of cable glands.
5. Wiring mistakes occur when junction
boxes and marshalling cabinets receive improper connections.
6. A frequent error occurs when common
and signal cables are mistakenly interchanged under MCC Interface termination
procedures.
7. Polarity Reversal in Analog Signals
Occurs Due to Incorrect Wiring of Signals.
8. The incorrect installation of
grounding and shielding stands as a major error in marshalling cabinets.
9. The incorrect setup of field
instruments includes wrong configuration of upper/lower range settings and
square root calculations together with offsets.
10.Control System Channel
Misconfiguration occurs when users select improper active/passive/3-wire signal
configuration settings.
11.The configuration of I/O modules can
fail because users set wrong range parameters or match tags incorrectly.
12.Fuse Issues: Blown fuse, missing fuse,
improper fuse rating, or open terminals.
13.Technical Failures Arise from
Incorrect Digital Signal Contacts When Users Choose Between Normal Open or
Normal Closed (NO/NC) Contacts.
14.Digital Output Signal errors arise
from the improper selection of dry contacts instead of wet ones.
15.The presence of unwanted voltage
inside dry contacts represents a Interrogation Voltage issue.
16.Incorrect component selection and
improper connections cause failures in relays as well as isolators and
barriers.
17.Incorrect Power Supply Module Sizing:
Improper power module or MCB (Miniature Circuit Breaker) rating.
18.The use of wires with improper colors
or sizes which fail to match requirements constitutes non-compliance in
internal wiring.
19.External Power Supply Oversight: Lack
of consideration for external power in 4-wire instruments.
20.The identification of these typical
mistakes in both FAT and site loop testing leads to better system reliability
and faster troubleshooting results.


