Thursday, October 10, 2019

OSDP an Access Control Protocol by SIA

OSDP an Access Control Protocol by SIA

ACCESS CONTROL WIEGAND PROTOCOL

In access control world we used Wiegand Protocol (Invented by John Wiegand in 1970). The communication protocol used in the Wiegand interface is called the Wiegand protocol. This protocol talks reader to controller. Basically Wiegand interface is a wiring standard used for interconnecting peripherals like fingerprint readers, card swipers or iris recognition devices. Initially created by HID Corporation, the Wiegand devices gained popularity thanks to the popularity of the Wiegand effect card readers of the 1980s. The Wiegand interface is considered a de facto wiring standard for card swipe mechanisms, especially for electronic data entry. Wiegand devices were originally developed by HID Corporation.
The Wiegand interface consists of three wires in the physical layer, the first wire is for ground and other two for data transmission, known as Data low/DATA0 and Data high/DATA1. The wires are composed of an alloy with magnetic properties. DATA0 and DATA1 are pulled up to high voltage, when no data is sent. When "0" is transmitted, the DATA0 wire is pulled to a low voltage while the DATA1 stays at high voltage. When "1" is transmitted, DATA0 stays at high voltage, whereas the DATA1 is pulled to a low voltage.

The most popular Wiegand interface is 26. It could be 3 bytes (Wiegand-26), 5 bytes (Wiegand-42) and even 7 bytes. Cable runs are limited to 500 feet. The Wiegand interface is unidirectional. It means that data is transferred in one direction only: from reader to the access panel. So access panel waits for a code on the line. If code is absent it means that there is no card near the reader or the reader is dead or the line is corrupted. To solve this problem in this way I asked one vendor to make a new firmware for its reader and now it sends each half an hour a "heart beat" code.
Given such limitations it has become increasingly clear that for reader technology and capabilities to progress, a bi-directional connection between the reader and access control system is a necessity. Some access control and reader manufacturers have recognized this need and developed proprietary bidirectional solutions. The OSDP a nonpriority interface specification that can be implemented without restriction. The protocol was originally developed by HID Global and Mercury Security Corp. in 2008 and adopted by SIA as a standard in 2011. SIA formed OSDP working groups, open to all members, and subsequent contributions have been provided by those participants.

What is OSDP
Open Supervised Device Protocol (OSDP) is an access control communications standard developed by the Security Industry Association (SIA) to improve interoperability among access control and security products. OSDP v2.1.7 is currently in-process to become a standard recognized by the American National Standards Institute (ANSI), and OSDP is in constant refinement to retain its industry-leading position. Open Supervised Device Protocol (OSDP) v.2.1.7 is a communications protocol that allows peripheral devices such as card readers and biometric readers to interface with control panels or other security management systems. It adds sophistication and security benefits through features such as bi-directional communication and read/write capabilities. The OSDP standard with Secure Channel Protocol (SCP) will support both IP communications and point-to-point serial interfaces, such as RS-485.

BI-DIRECTIONAL COMMUNICATION

The access control industry’s move to open standards is cultivating a broad range of interoperable products with enhanced features and security. Open standards also ensure that solutions can be easily upgraded to support changes in technology and applications, and give users the confidence that investments in today’s technologies can be leveraged in the future. OSDP with SCP specification provides bi-directional communications and security features for connecting card readers to control panels or other security management systems.
Bi-directional communication is particularly beneficial for enabling users to change configurations and to poll and query readers from a central system, which reduces costs while speeding, and simplifying configuration and improving the ability to service readers.

Unlike earlier unidirectional protocols, including the Wiegand interface and the clock-and-data signal approach used with magnetic stripe readers, OSDP enables continuous reader status monitoring. It can also immediately indicate a failed, missing or malfunctioning reader, as well as provide tamper detection and indication capabilities. All signaling is done over two data lines, providing the ability to use four-conductor cable to both power the reader and send and receive data. This lowers installation cost compared to the 6 to 10 conductors typically used for Wiegand.

HID Global is one of the first manufacturers to support OSDP with SCP in its reader portfolio as part of its iCLASS SE platform. iCLASS SE platform readers with OSDP enable central management, which lowers operational costs by making them faster and easier to configure and service.

SYSTEM INTEGRATION
OSDP gives Higher Security, Advanced Functionality, Ease of Use, More Interoperability. OSDP provides continuous monitoring of reader status, and can immediately indicate a failed, missing or malfunctioning reader. OSDP can also provide tamper indication for readers with onboard tamper detection capabilities. OSDP protocol for control panels to send messages for display to a cardholder via a screen embedded within or connected to the reader. The OSDP standard is particularly important for government installations because it supports high-end AES-128 encryption (required in federal government applications). And it meets the requirements of the Federal Identity, Credential and Access Management (FICAM) guidelines. OSDP also works with biometrics – Weigand does not.

SYSTEM ARCHITECHURE

Replacing legacy access control panels while maintaining operation with legacy card readers and other field devices.
When the need arises to replace or upgrade a card access or security control panel and if the new panel is OSDP compliant, it may be advantageous or necessary to convert the field devices to OSDP compatibility. This normally means replacing all readers, sensors, contacts, relays, and door control equipment to OSDP compliant versions as well. If this is not an immediate option due to time or cost constraints, the Cypress OSDP-1000 can provide an effective solution.

Credential Reader - Any Wiegand (Data 0 / Data 1), Strobed (Clock/Data), F/2F, or Serial interface can be handled by the OSDP-1000 when configured in "Reader Interface Mode". Since the format of the data is reported by the OSDP-1000 to the new control panel as an array of bits or characters, the panel's software must be configured to process the raw bit stream or character string. The reader type is configured by either on-board DIP switch or via OSDP configuration command from the panel.

Door Strike / Gate Operator - If the panel has provisions for multiple, dry-contact relay outputs and the panel's power supply is capable of driving the door or gate operator, then the 2 wires already in place to provide this function can continue to be used. Otherwise, since the OSDP-1000 is mounted in a secure location (not accessible from the un-secure side of the door or gate), it can be used to control the door or gate via OSDP command from control panel. If the control current is 1amp or less (at 12 to 24Vdc), the OSDP-1000's on-board, form C relay can be used. The new control panel will simply command the OSDP-1000 to turn the relay on or off. If higher currents are required, an external relay can be added. The power for the door strike, mag lock, or gate operator can be supplied from the panel (centralized power) or a local power supply near the door or gate (distributed power).
Sensors, Contacts, Switches, EOL Devices - Since the OSDP-1000 is mounted on the secure side of the door or gate, all remaining field wiring can be terminated at the OSDP1000. The new control panel will request data via protocol command/response and use it to determine the status of the door position switch, request-to-exit button, or motion detector. The OSDP-1000 has 2 Supervised alarm inputs to accomodate end-of-line resistor configurations. These can also be used as digital inputs.
Power Considerations - The OSDP-1000 does not magically create power for itself, the reader, or door strike from the twisted pair communication wires (but we might be working on it). The legacy panel or other power supply provided enough power to operate the reader, sensors, and door or gate operator. If the new control panel does not provide this power, then a suitable power supply must be installed at the panel location or at the door or gate. The OSDP-1000 only requires about 50ma and accepts a wide range of voltage (7 to 24Vdc). The reader, door strike, and any powered end-of-line device typically dictate what voltage to use (12 or 24Vdc).


All Devices - As mentioned earlier, converting all devices at the door or gate is recommended since this adds supervision of all signals. It also sets up the site for migration to an OSDP Control Panel in the future. Since the OSDP-1000 is mounted in a secure enclosure not vulnerable to tamper from the un-secure side of the door or gate, all signals can be terminated to it and supervised. The OSDP Reader has it's own polling address as does the second OSDP-1000 module configured for "Remote Interface Mode".
There still are many Weigand-base legacy systems in place and due to limited resources, it may take time to replace them all, but the migration is underway. Many organizations are taking a step-by-step approach replacing perimeter readers first and moving to interior readers as funding and time allow.


Future-proof your access control strategy today. Meet Signo, the signature line of access control readers from HID Global. This new reader line provides performance, versatility and security meet in a sleek, modern design. HID Signo™ Readers deliver mobile access capabilities, ensure easy migration from Wiegand to OSDP and support the widest range of credential technology so organizations can to upgrade at their own pace.

GROW YOUR BUSINESS
Integrators can differentiate from the competition by promoting open standard protocols, which can help build new customer relationships and win more projects by providing new found PACS features. With OSDP only four conductors are ever needed, two for power and two for all communication.
Wiegand does not allow for remote configuration or upgrade of a reader. OSDP enables a customer to remotely change the configuration of a reader (i.e. security keys or LED color) from any network-connected location.

BENEFITS OF OSDP
Compared to common low-security legacy protocols, the emerging OSDP standard offers:
Higher Security
·  OSDP is more secure than the most common access control communications protocol.
·     OSDP Secure Channel supports high-end AES-128 encryption (required in federal government applications).
·     OSDP constantly monitors wiring to protect against attack threats.
Advanced Functionality
·         Supports advance smartcard technology applications, including PKI/FICAM and biometrics.
·         Supports bi-directional communications among devices.
·         OSDP supports advanced user interface, including welcome messages and text prompts.
·         OSDP’s use of 2 wires instead of 12+ allows for multi-drop installation, supervised connections to indicate reader malfunctions, and scalability to connect more field devices.
Ease of Use
·         Audio-visual user feedback mechanisms provide a rich, user-centric access control environment.
·         Guesswork is eliminated since encryption and authentication are predefined.
·         Low cost of implementation on an embedded device.
More Interoperability
·         Using OSDP enables communication among different manufacturers' devices and solutions.
·         The standard applies to peripheral devices (PDs) such as card readers and other devices at secured access doors/gates and their control panels (CPs).
·         SIA promotes the standard at regular “plugfests” among manufacturers and at InteropFest – an annual interoperability event held at ISC West tradeshow every spring in Las Vegas, Nevada.
·         The OSDP specification is currently recommended when TCP/IP, USB, or other common protocols do not lend themselves to the application.
·         The OSDP specification is extensible to IP environments and the OSDP WG is working on deploying OSDP over IP soon.

Ref:
https://ipvm.com/reports/osdp-access




8 comments:

Bob Dolan said...

This Bringing New Functionality to Multi-supplier Access Control compile ONVIF Profile A. It’s also important to note that Profile A and other access control standards, such as the Security Industry Association’s OSDP that allows access control readers to interface with control panels or other security management systems, aren’t competing with one another, but rather are complementary. ONVIF Profile A and OSDP can co-exist within the same access control ecosystem and can both provide benefits. This synergy between ONVIF Profile A and other standard interfaces allows end users to implement technology that is driven by their specific needs, rather than by a single standard or proprietary brand approach.

John Lewis said...

CEM eDCM 350 (Door Control Module) is a low cost, intelligent two-door IP controller that is designed to interface to Open Supervised Device Protocol.

PACOM 8603 intelligent IP door controller and I/O module is built using expansion modules it supports cards using the Open Supervised Device Protocol.

The PW6101 series controller and reader module is a high performance. The controller and reader module are configurable for either Wiegand or OSDP. PW6K1ICE is a full featured PoE single door access controller maximum of 16 PW6K1R1E PoE reader modules. Minimal training required for persons familiar with PW6000 and Pro-Watch.

Telcred supports door controllers from Axis Communications. Axis door controllers support a wide range of readers that can be connected with either OSDP (Open Supervised Device Protocol) or Wiegand. They can be powered over Ethernet (PoE) and connected simply and securely to the Telcred service through a technology called O3C (One Click Connection Component) developed by Axis. In the future, Telcred will support open, IP-based door controllers also from other suppliers, when they become available in the market.

Santa Ram Pandey said...

Excellent Blog! I would like to thank for the efforts you have made in writing this post. I am hoping the same best work from you in the future as well. I wanted to thank you for this websites! Thanks for sharing. Great websites!

Anonymous said...

I have no words to appreciate this post. It is just an outstanding source of knowledge on this blog.

No Name said...

Hey Guys !

USA Fresh & Verified SSN Leads with DL Number AVAILABLE with 99.9% connectivity
All Leads have genuine & valid information

**HEADERS IN LEADS**
First Name | Last Name | SSN | Dob | DL Number | Address | City | State | Zip | Phone Number | Account Number | Bank Name | Employee Details | IP Address

*Price for SSN lead $2
*You can ask for sample before any deal
*If anyone buy in bulk, we can negotiate
*Sampling is just for serious buyers

==>ACTIVE, FRESH CC & CVV FULLZ AVAILABLE<==
->$5 PER EACH

->Hope for the long term deal
->Interested buyers will be welcome

**Contact 24/7**
Whatsapp > +923172721122
Email > leads.sellers1212@gmail.com
Telegram > @leadsupplier
ICQ > 752822040

Riajengenelen said...

Hello everyone, Are you into trading or just wish to give it a try, please becareful on the platform you choose to invest on and the manager you choose to manage your account because that’s where failure starts from be wise. After reading so much comment i had to give trading tips a try, I have to come to the conclusion that binary options pays massively but the masses has refused to show us the right way to earn That’s why I have to give trading tips the accolades because they have been so helpful to traders . For a free masterclass strategy kindly contact (paytondyian699@gmail.com) for a free masterclass strategy. He'll give you a free tutors on how you can earn and recover your losses in trading for free..

Anonymous said...

SIA OSDP is an access control communications standard developed by SIA to improve interoperability among access control and security products. Maintained and developed by the SIA OSDP Working Group since 2011, the standard was submitted to the IEC as a candidate standard in 2016.

“This is really exciting for the industry,” said Anthony Diodato, co-chair of the SIA OSDP Working Group and founder and chief technology officer at Cypress Integration Systems. “While the process may have been long, the industry can finally point to an international standard that brings higher security and greater functionality to new and legacy access control solutions.”

In the coming weeks, SIA will release a mirror standalone document to the IEC standard – OSDP 2.2 – which will replace SIA OSDP 2.1.7 and be available in the SIA store.

“SIA OSDP is an excellent example of how various industry stakeholders can come together to contribute and collaborate on a pivotal international technology standard that provides real business and operational value to the industry,” said Steve Rogers, co-chair of the SIA OSDP Working Group and president at IQ Devices.

The news of international standardization comes soon after SIA announced various other tools and services to promote interoperability and education around the OSDP standard, including OSDP Verified – a comprehensive testing program that validates device conformance to the SIA OSDP standard and the related performance profiles – and the OSDP Boot Camp series, which offers OSDP training for system integrators and practitioner teams. These OSDP advancements have been a team effort within the SIA OSDP Working Group, and SIA particularly acknowledges Rodney Thayer, convergence engineer at Smithee Solutions, for critical engineering and technical support as the project progressed through the IEC submission and approval process.

Anonymous said...

OSDP Approved by IEC as an International Standard
The SIA Open Supervised Device Protocol (OSDP) standard – developed by the Security Industry Association (SIA) – has been approved by the International Electrotechnical Commission (IEC) technical committee on alarm and electronic security systems as an international standard. The latest version of SIA OSDP will be listed as IEC 60839-11-5 and be available in the IEC Webstore.