Components of BMS
A Building
Management System (BMS)—also known as a Building Automation System (BAS)—is a
computer-based control system installed in buildings to monitor and manage the
Mechanical, Electrical, and Electromechanical services. These services
typically include:
·
HVAC (Heating,
Ventilation, and Air-conditioning or all supply and exhaust fans, ACs
etc.).
·
Lighting
control system.
·
Fire
alarm system.
·
Firefighting
system.
·
Security
control system.
·
Lift
control system.
·
Pumping
system.
·
Water
tanks level.
·
Irrigation
system.
·
Electrical Energy meters.
·
Water
Leak detection system.
·
Split
units.
·
VFD-Variable
frequency drives.
·
VRF/VRV-Variable
refrigerant flow or volume (both are same but each term copyrighted by a
different vendor)
·
And
any other system which has provision for BMS to control and monitor.
The
primary goal of a BMS is to ensure efficient, safe, and reliable building
operations, while also optimizing energy consumption and reducing operational
costs.
Architecture
Overview
Typical
BMS Layout
[ Sensors ] ↔
[ DDC Controller ] ↔ [ BMS Server/SCADA ] ↔
[ Operator Workstation ]
Major
Components
✓Water Quality Sensors is analyze chemicals, pH levels, and other water parameters for environmental management.
✓Air
Quality Sensors is measure gases like carbon monoxide to control ventilation
system
✓Digital
Sensors report on/off status, such as door contact switches or flow switches,
or send pulses for counting events like water flow.
✓Analog Sensors provide a continuous, variable output, like thermistors or 0-10V signals, for detailed measurements of temperature, humidity, or pressure.
Actuators execute commands from controllers to adjust mechanical operations.
Type Function
✓Valve Actuators Open/close water or air valves
✓Damper Actuators Control air flow in ducts
✓Relay Modules Turn on/off electrical loads
🔸 3. Controllers (DDC – Direct Digital Controllers)
✓Controllers process inputs from sensors and determine outputs to actuators.
✓Local controllers: Installed near equipment (e.g., AHUs, chillers)
✓Programmable: Logic can be customized per application
✓Real-time processing: Executes control loops continuously
✓Supports communication: Modbus, BACnet, or proprietary
Panel
Element Description
✓DDC
Controller Main logic unit
✓Terminal
Blocks Wiring terminations
✓Circuit
Breakers Protection for I/O modules
✓Relays
and Contactors For switching loads (pumps, fans)
✓24VDC
Power Supply Supplies power to controllers/sensors
🔸
4. Field Devices
Combination of
input/output modules, power supplies, fuses, and interface terminals mounted
inside control panels.
✓Analog
Input (AI): e.g., 4-20mA, 0-10V sensors
✓Digital
Input (DI): e.g., dry contact, flow switch
✓Analog
Output (AO): e.g., control signals to valves
✓Digital
Output (DO): e.g., relay signal to pump/starter
🔸
5. User Interface Devices
a) Operator
Workstations
b) Touch Panels / Mobile Apps
🔸
6. Network Infrastructure
BMS requires stable
communication between field devices, controllers, and servers.
Type Example
✓Serial
RS-485 (Modbus RTU, BACnet MSTP)
✓Ethernet/IP
BACnet/IP, Modbus TCP
✓Fiber
Optic Backbone for large campuses
✓Wireless
Wi-Fi, LoRaWAN, Zigbee (modern IoT)
🔸
7. Server & Database System
🔸
8. SCADA/GUI Software
Extra innings - Real-Time
example for BMS System
Any modern-day building client provides huge specifications for BMS System,
Whereas here I am going to take simple requirement to monitor and control the sequence of Air Handling Unit.
Let us see below the requirement of the client to monitor and control the sequence in BMS System.
Before we go detailed about how to design the BMS System for the requirement, let us see some basics components of the AHU-Air handling unit.
AHU is an HVAC system which consists of the duct, fan, filter, cooling coil, heating element, humidifier, sound attenuators, dampers, valves and many more to regulate the air into the room by heating, ventilation and conditioning to distributes the conditioned air through the building and returns it to the AHU and also called as centralised AC in modern-day building.
Duct – It is the collection of
metallic tubes that interconnected and distributes the heated/cooled air to the
required rooms.
To monitor the duct air temperature in fresh, return and supply duct. We have to install the duct temperature sensor in the duct.
Fan Motor– Blower is used to circulate the air
from fresh and return duct to the supply duct.
This fan
motor controlled and monitored by the separate electrical panel by the designed
electrical circuit with the help of electrical relay
and contactor and providing an option to BMS system to
On/Off the
fan.
Monitor
the fan running status.
Monitor the Fan motor overload fault status and many more.
Filter– It is one of the main components in AHU to prevent the dust and dirt particles from entering in the AHU.
When the AHU fan motor started, the fresh outside air supplied into the duct where filter components used to filter the dirty particles continuously and to monitor the filter extreme dirty condition.
DPS switch is used to install across the filter and provide signals to BMS,
when the filter gets dirty(technically DPS-Differential pressure switch will send the signal to BMS when the pressure reached more than pre-set across the filter, and this same function can be used to monitor the fan status.
Heating/Cooling element- It is used to cool or heat the water that entered in the coil so that air in the duct can be heated or cooled based on the user requirement.
Either heating or cooling water enters into the coils are controlled and monitored by valves on the pipe with the help of the valve actuator.
Dampers- An HVAC damper is a movable
plate, located in the ductwork, that regulates airflow and directs it to areas
that need it most.
Damper opening and closing position-controlled electrically with the help of damper actuators, and these actuators have terminal for control from BMS and terminal to monitor the feedback of position.

No comments:
Post a Comment