Showing posts with label BACNet. Show all posts
Showing posts with label BACNet. Show all posts

Monday, February 1, 2021

DDC in BMS System

 DDC or Direct Digital Controller in BMS System

What is DDC ?

To understand the DDC, we need to know a little bit of history about what was the things before the DDC invention and why it was invented? So that we can have a broader view of the primary purpose of DDCs.

The Programmable Logic Controller or PLC used to control and monitor the Process mainly in the industry like automobile and other manufacturing factories.

Richard Morley invented PLC in 1968 to fulfil the primary needs of control and protect the production capacity of machines and manufacturing lines in the industry, and this PLC used initially was in the area of transfer lines in automotive plants.

Due to these PLC or Programmable logic controllers were designed and invented mainly for controlling and monitoring or automating the productions in the industry.

But when it comes to buildings, this PLC cannot fulfil the exact needs in terms of tenants comfort, environmentally green or can say effective management system for buildings. And still, we can use PLC for Building automation whereas it will be an excessive investment and different performance.

So here DDC or direct digital controller invented in order the process and automated the building equipment needs almost which PLC can do with minimal investment from installation to engineering.

What is the Main Difference between PLC and DDC?

What is DDC or Direct Digital Controller?

In a nutshell, DDC is a controller which use the analogue or digital signals from various devices of a field sensor and actuators and then process and control the system based on the programme written inside the controllers and has the capability to sends the information to another controller or DDC.

Basic Features of DDC

·       DDC or Direct digital controller usually has the followings features

·       The Analogue Inputs is to monitors the fields sensors values.

·       Digital Inputs to monitors the on/off status from switches/contactors.

·       The analogue output is to control the field actuators devices.
Digital Output is to control relay or provide low voltages.

·       DDC must have internal ROM/RAM to store control logic and sensor values.

·       It must have networking protocols inbuilt to transfer the data between the devices.

·       Modern DDC controller should have the capability to implement BACnet protocols for communication.

Note that there are various DDC controllers available in the market from the different manufacturer and those DDCs are available with a variety of function and features based on the specific needs like controller has all inputs/outputs like Analog inputs, Digital input, analogue output and digital output and some controller has only digital/analogue inputs.

Let us see below DDC Controller

·       Eleven 10-bit universal inputs whereas we connect either analogue input or digital input using a jumper select, eight binary outputs, and eight analogue outputs.

·       Terminal 23,24 used to connect other DDC controller to communicate between devices through BACnet over MSTP.

·       It has non-volatile memory used to store program and work independently.

·       It has the 24vdc used to give power for field devices.

Now Let us see how DDC used to control the BMS System,

Consider the followings scenario which we need to control and monitor through above DDC.

Let us say in Building, we need to control Pump control and control filling sequence through DDC whereas we have 2 Booster pumpS, one is for filling the water tank and other is to pump the water to buildings purpose to tenants like toilet etc.

This two-pump motor is controlled through the pump control panel by manually and it should work automatically based on the following sequence 

·       Pump-1 should run if the water level below the high level and stops once above the high level.

·       Pump-2 should run if the pressure on the supply line lesser than the defines let us say 2.5bar.

·       Pump-2 Should not run if water lesser than the lower level switch even pressure lesser than defined.

So based on the above sequence we will have following parameters to monitor and control

·       Booster pump-1 Run status from control panel-Binary Input

·       Booster pump-1 Run command from control panel-Binary output

·       Booster pump-2 Run status from control panel-Binary Input

·       Booster pump-2 Run command from control panel-Binary output

·       Water Low-Level status-Binary Input

·       Water High-Level status-Binary input

·       Liquid pressure on supply line-Analog Input

Let us connect the above points in DDC Controllers as follows

BP-1 Run sts- IN-1

BP-2 Run sts- IN-2

Low-Level Sts- IN-3

High-Level Sts-IN-4

Liquid Pressure-IN-5

BP-1 Run Command-BO-0

Bp-2 Run Command-BO-1

 

Logic will be as follows to execute the above sequence

 

If IN4==1        ##(means lesser than high-level status)

then

BP1=1             ##(On Pump)

else                 ##(means above than high-level status)    

BP1=0             ##(Off-Pump)

endif

 

If (IN5<2.5 and IN4==1)    ##( if pressure lesser than 2.5bar and water above the low-level sts)

then BP2=1     ##(on Pump)

else

BP2=0             ##(Off-Pump)

endif

 

Note that this program may change for each vendor controllers.

Not only this small sequence but also DDC can execute complex and critical sequence in BMS System for HVAC.


Saturday, August 24, 2019

SSA Integrate - Fire alarms and BAS

SSA Integrate - Fire alarms and BAS

The integration of Building Automation System and fire alarm systems can result in overall reduction in equipment, installation, and maintenance costs while still maintaining the level of safety required for these systems to operate. 

With the advent of smart building technology, heating, cooling, electrical, lighting, security, and other systems need monitoring and intercommunication for optimized efficiency and operation. With sophistication comes the need for a building automation system (BAS) to allow for nearly seamless operation of these various interrelated equipment.
When the fire alarm system takes control of equipment that is not a listed component of the fire alarm control unit, the fire alarm system must either override the natural operating mode of the building equipment or pass off that command via a simple switch or data communications to the building mechanical systems. Likewise, each manufacturer’s BAS has its own protocol for monitoring conditions and communicating operational commands to maintain the proper building environment and efficiency. There are also standard open communication protocols such as LonTalk and BACnet that can be used to communicate with a multitude of equipment from various manufacturers in order to achieve an integrated building system. 
The communication protocol for a fire alarm control unit to communicate to and from its indicating (input), initiating (output), and sometimes notification appliances is typically an analog or digital communications signal carried over what is referred to as a signaling line circuit (SLC). Because communications signals are typically proprietary protocol, each SLC is dedicated to a specific manufacturer’s equipment and cannot include connection of incompatible devices that use a different signal protocol.
Therefore, in order to integrate system alarm and control functions with the BAS in a manner other than relay logic, fire alarm system manufacturers had to also design and support the open communication protocols used for building automation, in a manner that would not compromise the integrity or the operation of the fire alarm system. This process of sharing information between both fire alarm and BAS came to be known as bridging, or open gateway processing. Because of the strict code and listing requirements of fire alarm systems, much of this communication has been primarily limited to one-way communication. However, some manufacturers of both fire alarm and BAS do produce equipment such as gateways that are listed for bi-directional communication with their equipment. 

Make a case of a building with separate building automation and fire alarm systems: When the building engineer receives a call from an occupant complaining about increased temperature or whistling air within the ductwork and finds that the fan is shut down or a damper is closed, the building engineer is more apt to call a controls contractor to investigate the problem before he calls their fire alarm service provider. Should the problem be related to an override of controls by the fire alarm systems, not only does the building engineer have to wait for the controls contractor to diagnose the problem, he also has to call the fire alarm contractor to come out and fix the problem. This process can take time to correct; meanwhile, building occupants are uncomfortable and inconvenienced.
Sometimes this can even lead to finger-pointing between the two service providers as to whose problem it really is. In this scenario, the fire alarm control of a fan or a damper is required to be ahead of the hand-off-auto switch for the power to the equipment so the inadvertent shutdown of the equipment does not inhibit the operation of the fire alarm feature. A failure of the fire alarm system control relay could shut down the fan or close the damper without an alarm being present on the fire alarm system or fault condition occurring on the fire alarm control unit. 

Because many components that affect air and smoke movement within a building are shared between HVAC and fire alarm systems, let’s take a step backward in the evolution of the building process. When building systems are being commissioned for proper operation by either an authority having jurisdiction (AHJ) or an independent third-party group, coordination must occur between multiple trades. At this point in the construction process, each trade is independently looking to complete its own scope of work and more often than not is under pressure to finish the specific scope in a designated timeframe. Sometimes this leaves a disconnect between the fire alarm and mechanical trades that results in disruption during start-up and commissioning. 

The integrated system approach allows for those individuals responsible for controlling air movement to be focused on proofing and balancing the mechanical system, while the fire alarm contractors focus on the detection and annunciation of the alarm events. Much in the same manner as referenced in the previous example, the problems can get resolved more expeditiously and the systems can be brought on-line. 

If we focus on the installation of a building management system (BMS) and a fire alarm system, we see many similarities. Each of these control systems is classified as low-voltage systems that communicate to their respected devices through an analog or digital signal. Their wiring methods and materials are similar, and often their respective equipment is located in the same general area and is performing the same basic functions with one significant difference: the fire alarm system uses individual point addressable monitor and control modules while the BAS uses digital input/output driver assemblies that communicate with different protocols. 
Why is this important? Because the BAS still requires individual pairs of conductors to each point being controlled or monitored by the digital input/output module, resulting in more wire being needed and longer installation time.

When considering SSA system integration, the ability of the BAS to control a smoke control system operation falls under the auspice of the jurisdiction’s building code, often based on the model building codes. The IBC has been adopted by a large portion of the United States and is used in this article as an example. IBC Section 909 covers smoke control systems, the procedures for determining system parameters, the acceptable methods that may be used to accomplish smoke control, and the requirements to document the system’s actual performance. It recognizes that the smoke control system is a life safety system and must maintain the same high level of reliability required for any type of fire protection or fire alarm system.

Section 909 requires smoke control systems to be initiated by sprinkler system or smoke detection system operation, depending on the type of system being designed. It also requires systems providing control input or output to the mechanical smoke control systems to comply with Section 907 (Fire Alarm and Detection Systems) and NFPA 72: National Fire Alarm and Signaling Code, and states that such systems must be equipped with a control unit that complies with UL 864 and has to be listed as smoke control equipment.

Using a fire/smoke damper that is part of an engineered smoke control system complying with International Building Code Section 909 as an example, at each damper location we have a smoke detector for detection of smoke, an actuator that controls the opening and closing of the damper, and an end switch to provide positive confirmation of the damper open and closed position. Because the fire alarm system already needs to have circuitry to this location for individual smoke or duct smoke detectors, that same pair of wires can be used to monitor the open and closed position of the damper, essentially eliminating two pairs of wires back to the BAS controller. The position status signals of the damper can then be transmitted from the fire alarm system, through the gateway, and into the BAS along with the active alarm point information. This leaves the wiring to the actuator as the only BAS wiring needed at the damper location.
As another example, let’s use a stairway pressurization fan that is being controlled by a variable frequency drive (VFD). Typically, a VFD would be connected to the BAS via a digital signal while the fire alarm system would provide override of the VFD using dry contacts to stop it or put it into a smoke mode condition. Allowing the BAS to perform all of the control functions permits the adjustment of the fan speed through the BAS to regulate for atmospheric conditions by employing other equipment connected to the BAS, such a digital differential pressure sensors. Using the BAS solely for control eliminates any connection to the fire alarm system, with the activation commands being sent through the gateway.

Taking advantage of the aforementioned efficiencies gained by integrating the BAS with the fire alarm system requires planning in the design process. This planning process is the same whether it is a design build or a design assist type of project delivery. The building owner and operator must be involved in the process of establishing the design criteria or at the least have influence over it. In a typical design build or design assist process, the integration of these two systems is an afterthought and often never considered. The end user must be made to understand that the efficiencies gained by integration will pay dividends long into the lifecycle of the building.

Integrated systems require enough time to test and to verify that the system interoperability is functioning properly. It is important that the engineer as well as the installing contractor and the equipment vendors understand the impact of these requirements on providing an approved and code compliant installation. 
Due to the complexity of these systems and the required integration, testing must confirm that the functions and sequences work correctly under both automatic and manual modes.

The inspection and testing of integrated systems is usually exasperating and time-consuming, and often requires multiple rounds of retesting before all the deficiencies are corrected. This is often caused due to all of these different systems being completed late in the schedule and not enough time to “get the kinks out” prior to final testing. Anything that can expedite the commissioning process is beneficial to the overall project. 

One of the advantages of using the BAS as an integrated part of the smoke control system is the system’s ability to modify operating conditions to accommodate actual ambient conditions through the use of VFDs. The design of smoke control systems is based on many variable conditions, including temperature, wind conditions, and the quality or “tightness” of the construction. These conditions tend to make testing and adjusting of the smoke control system difficult at best.

Integrating BAS can help minimize test stress by adjusting the fan speed of individual fans through programming. In a situation of excessive stair pressurization, the individual fan can be adjusted to limit its airflow to the stair, resulting in a lower level of pressure affecting door opening forces. Similarly, for individual zone smoke control system performance, the fan speed can be adjusted on a zone-by-zone basis, based on the fire alarm signal received by the BAS. 

The downside to this operation is that the BAS controls are typically located remotely to the fire alarm control panel and the firefighters’ smoke control panel, both of which normally reside in a fire command room. BAS controls and system components are usually located for the convenience of the building’s staff and HVAC equipment. Under test conditions, additional personnel may be required to monitor the BAS controls to make any required modifications. 

While modifying fan output for each smoke zone condition is a more expedient method to obtain approval, it also provides future opportunities to inappropriately change the settings, possibly making the system ineffective. Care must be taken to limit access to this programming and provide logging procedures to document when and why changes are made.
Take a note: Fire condition is determined by the Fire Alarm Control Panel. AHU will automatically shutdowns the whole system with associated interlocks.

Question: How can the reliability of the fire alarm system be maintained while mixing data with other non-emergency inputs?
Answer: In reality the fire alarm system reliability is unaffected by other integrated systems when using the BACnet protocol due to the required use of the gateway interface. The gateway keeps the other signals on the network form affecting the fire alarm system.

Question: Building automation systems are more and more residing on an owner's IT network. If a BACnet gateway is used to interface to the fire alarm system, instead of hardwired connections, this device would reside on the owner's network which is likely not UL listed. Have you come across this concern?
Answer: The BACnet gateway itself is required to be listed, but not the system. So the fire alarm system devices or zones would be connected to the listed gateway and then the other side of the gateway would be connected to the network allowing the objects to be transmitted to the BAS, for example. Once again we are still required to use the listed gateway as the interface but the balance of the non-fire alarm system equipment does not need to be listed for fire alarm use. Having said that there are changes proposed to NFPA 72-2019 that would allow direct connection to the Ethernet or a network under certain conditions. These proposed changes have not yet been officially adopted.

Question: Do you recommend integrating the building fire alarm system and the BAS in an office building that undergo tenant fit-outs on a continuous basis?
Answer: With any system design in any building or occupancy planning is imperative. Knowing beforehand that the occupancy is to be offices and knowing that tenant fit-out occur on a regular basis, it is incumbent on the original system designer to include system changes and expansion in his or her design. Just because frequent changes to a system are expected does not preclude integrating all of the systems. It does require more coordination and provided that happens the systems should remain reliable.

Question: Does OEO override designated and alternate recall operation?
Answer: No, just the opposite. All recall features (elevator lobby smoke detectors for example) would input to the OEO controller and it would relinquish OEO or those floors in recall.

Question: How would elevator shunt trip for a sprinkled hoistway or elevator equipment room operation work into the OEO sequence of operation?
Answer: As stated previously, when these types of operations occur during or prior to OEO, these operations would take priority over the OEO and all OEO for the affected elevators would cease and all signs and voice messages would revert to “Do Not Use The Elevators, Use The Stairs” operation. 

Question: How would the use of BACnet interface to emergency control systems, requiring supervision of control wiring, address this code requirement?

Answer: NFPA 72-2019 (and previous editions) require supervision to within 3 ft of the controlling device or no supervision if the device operation is fail-safe, meaning if the connection to the device is severed, the emergency device operates as required. The gateway could be determined as the connection to the controlling device and as long as that was within 3 ft of the controller it would be considered code-compliant. This is unlikely to happen and other design considerations will need to be considered to ensure that the performance of the emergency control system is code compliant. Given the many types of configurations, there can be no one definitive answer to the problem until the actual field condition is evaluated.

Sunday, July 28, 2019

Procure BACnet System

Procure BACnet System

BACnet was designed to allow communication of building automation and controlsystems for applications such as heating, ventilating, and air-conditioning control (HVAC), lighting control, access control, and fire detection systems and their associated equipment.
The UDP port number 47808 (in hexadecimal, X'BAC0') identifies BACnet messages and is the UDP port used by PAD devices. BACnet/IP devices use this UDP port by default but may be configured to use a different number if necessary. An open protocol should be powerful and robust, capable of meeting all future communication needs, as well as the present needs throughout all system levels. Any communication protocol which doesn't meet these criteria should be eliminated from further consideration.

BACnet's open structure and object-oriented commands enables developers to provide enhancements or features, while still maintaining full interoperability for all core operations. If use of a new control feature becomes widespread and there is a need for it to be standardized among vendors. ASHRAE provides a procedure for it to be adopted as a standard BACnet object or service.
BACnet is a widely accepted, non-proprietary open protocol standard. Companies began announcing their support for BACnet even before the final draft of the standard was released. The fact that ASHRAE developed BACnet plays a significant role in this acceptance. ANSI perceived BACnet to be a significant development and adopted it as a protocol standard within months of acceptance by ASHRAE.
Components vs Systems
For many years the BACnet community has worked hard to ensure that BACnet is a global standard and that it’s implemented consistently across multiple supplier product lines.  BACnet International devotes substantial resources to the BACnet Testing Lab (BTL) and to annual device “plugfests” to support that objective.  We regularly point out that BACnet is a global consensus standard and we trumpet the value of standards.  We talk about component interoperability and in some cases even interchangeability.  All of this is good.  Users need to understand the power of standards and how specifying systems that incorporate BACnet can add value to their building automation investments.  However, by promoting BACnet as standard and then using the shortcut term “BACnet System” we invite the unschooled to mistakenly extend the concept of “standard” from the communications protocol to the system.  That seems to lead some of them to the conclusion that all “BACnet Systems” are essentially equivalent and can be procured like commodity products … even to the point of the “reverse auction” procurement process for an energy management system I recently encountered. 

Reverse Auction Procurement
Reverse auctions have been around for more than a decade.  They evolved as a “simple” way for buyers to drive down the cost of components.  The essence of reverse auctions is that suppliers bid back and forth for a well-defined piece of business on the basis of price.  Full-featured web platforms have evolved to support this purchasing model but, even so, it has its limitations.  One of the biggest limitations is that for it to be effective, the product and its associated transaction attributes (e.g. lead time, delivery date, etc.) need to be unambiguously defined in terms that can be readily measured.  And therein is the rub.  Energy management and building automation systems are complex so fully defining all of the important attributes is a huge challenge.  Leaving any important attribute undefined results in suppliers compromising on those unspecified attributes to achieve the lowest cost and win the business.  On the surface the result might look like a good deal for the buyer.  But those compromises might well come back to haunt the buyer in the long run.


Lessons Learned
It was an attempt to give people new to the BACnet community some insights based on the experience of people who have already designed and operated systems built around BACnet.  One of those “lessons learned” was that a “BACnet System” is still a system. The BACnet standard can make system integration faster, simpler and more effective but it is not a substitute for system expertise, creativity or design rigor.  Nor does BACnet provide any assurance of product quality or system effectiveness.  These come only through knowledge and experience.  So, I encouraged owner/operators to develop a partnership approach to working with suppliers who have that knowledge and experience. I saw first-hand what happens when complex systems procurement is driven from a “first cost” perspective without sufficient focus on supplier partnerships.

Benefits of BACnet Protocol

  • Single operator workstation for all systems
  • competitive system expansion.
  • Eliminates fear of being an owner to be locked in with a single vendor.
  • Possibility of integrating all BAC Functions.
  • Interoperability
·         Data sharing
·         Alarm and event management
·         Trending
·         Scheduling

·         Remote device and network management

Summary
BACnet is a standard. All the necessary elements are in place: strong customer demand, a robust open standard and manufacturer's support of the standard. BACnet seems to provide a complete solution to interoperability issues for building procurement  team.  Understanding the difference is important in establishing a procurement process that builds positive supplier relationships and generates maximum value in acquiring an energy management or building automation system. SSA Integrate can guide how to utilize this.


Sunday, April 14, 2019

Know about BMS technical protocols

BMS - What you should know about technical protocols

If you or a client is choosing a building management system (or BMS), it’s important to understand how it communicates information with digital devices such as controllers, meters, and input/output boards, and computers.

The details are important because some BMS use languages—or technical protocols—that lock you into using their vendor’s proprietary technology. Use of such protocols may force you and your client to pay higher prices for software and hardware available from only one vendor or its licensees.

This article describes common categories of BMS protocols. It recommends that you avoid proprietary protocols and favor more open ones.

A BMS communicates through protocols
To exchange data, digital devices must use a common data structure and a common channel or medium of communication.

The figure below shows a master BMS that communicates with devices that use microprocessors. They include a roof-top unit (or RTU), refrigeration controllers, energy meters, and other input/output boards within a building. The building controller also uses the Internet to share temperature, operating parameters, or energy data with remote users through enterprise servers or personal computers.
A BMS protocol defines the format and meaning of each data element, in much the same way a dictionary defines the spelling and meaning of words.

The data exchange often occurs through a physical wire such as a twisted-pair RS485 or an Ethernet CAT5 cable). It may also occur wirelessly over wi-fi network, through an internet protocol (or IP).
The phrase “BACNet over IP” means the BACNet protocol communicates through an IP network.
Some protocols are more open than others
Protocols fit in one of four categories, depending on their relative “openness:”
1.       Open. The protocol is readily available to everyone.
2.       Standard. All parties agree to a common data structure. The protocol may be an industry standard, such as BACnet and Modbus.
3.       Inter-operable. The protocol is vendor agnostic. A controller from one vendor can replace one from a different vendor.
4.       Proprietary. The data structure is restricted to the creator of the device.

Why you want BMS with open protocols
A BMS with proprietary protocols locks the system owner into using a single BMS vendor. For example, you can’t remotely change the set points of a proprietary BMS unless you use the vendor’s software.
In contrast, with open and standard BMS protocols you can shop for alternative providers of digital devices and enterprise software.

This is why use of proprietary protocols is inconsistent with best practice. The lesson is clear:
In choosing a BMS, be sure its protocols are not proprietary.

How to know whether a BMS protocol is open
To determine whether a BMS protocol is open, ask the vendor two simple questions:
1.       Can your competitors exchange data with your BMS?
2.   Is the system’s protocol published in such a way that it’s easily accessible to everyone (including competitors)?

Best open protocols: BACNet, Modbus, and XML
For a master controller that exchanges data with devices and meters within a building, prefer the BACNet, Modbus or any other standard protocol. Otherwise, make sure it’s at least open enough so anyone with proper security access can read and write information.

For remote enterprise access (protocol B in the figure), organizations often use BACnet over IP.
The current trend is toward use of additional Internet technologies. Companies like Honeywell Tridium (Niagara framework) and many others have exchanged data through standard internet eXtensible Markup Language (or XML) with web services.

Even the ASHRAE BACNet committee has convened a working group to define use of XML with BACnet systems. The group is also working to define web services that will enable data exchange between building automation and control systems and various enterprise management systems.

Put in short, use these criteria when you’re choosing devices and BMS:
·         For devices such as RTUs and refrigeration controllers, look for ones that use open protocols such as BACnet or Modbus.
·        Make sure these devices give you both “read” and “write” capabilities so you can change set points.
·         For easy enterprise access, choose a BMS with web services and XML capabilities.
·         Make sure the web services of the BMS allow both read and write capabilities.
·      Be sure the BMS supplier provides the XML dictionary and definitions of web services to anyone, including competitors.

 
This Artical published on April 2019 at Safe secure Magazine.

Friday, October 20, 2017

Building Automation Protocol selecting

Building Automation Protocol selecting

Each of the competing protocols claims to be the best. So how do facility executives select the one that is best suited for the facility?

Data is communicated between devices through a Communication Protocol. It is the language that a particular device is able to interpret and forward to other devices on the network. Some common protocols are BACnet, Lon, and Modbus.

Protocols must be selected based on the needs of the facility and its ability to support a particular protocol. Each has been used many times to implement an interoperable system. Each has its advantages and disadvantages. Involve your information technology department. They generally are the controlling agency for the facility’s network infrastructure.


When selecting a control system choose one where the front end is compatible with a number of protocols. This will give greater flexibility as building equipment and devices change over time.

Why you want a BMS with open protocols
A BMS with proprietary protocols locks the system owner into using a single BMS vendor. For example, you can’t remotely change the set points of a proprietary BMS unless you use the vendor’s software.
In contrast, with open and standard BMS protocols you can shop for alternative providers of digital devices and enterprise software.

Building Automation Controls Network (BACnet): BACnet is a network protocol specifically used for multiple devices to communicate across building automation systems by system users and building system manufacturers

Modbus: Modbus is a network protocol best used for industrial automation systems specifically for connecting electronic equipment. Although Modbus is best for industrial applications, its simplicity allows it to be a useful tool for building automation as well.


LonWorks: LonWorks is a communication network protocol useful for building automation applications designed on a low bandwidth, for networking devices through power lines, fiber optics, and other media.

Protocol
BACnet
Modbus
LonWorks
Full Name
Building Automation Controls
Serial Communication Protocol
Local Operational Networks
Developed By:
ASHRAE
Modicon Inc.
Echelon Corporation/ Motorola
Use
Communication across devices
Connection between devices
Networking devices through power lines, fiber optics, and other media
Markets
Industrial, Transportation, Energy Management, Building Automation, Regulatory and health and safety
HVAC, Lighting, Life Safety, Access Controls, transportation and maintenance
Home automation, industrial, transportation, and public utility control networks.
Examples
Boiler Control, Tank Level Measurements
Tasks such as request temperature reading, send status alarm, or fan schedule
Security, lighting systems, HVAC, machine control, manufacturing, metering
Proprietary
No
No
Yes
Transmission Modes
Ethernet, IP, MS/TP, Zigbee
ASCII, RTU, TCP/IP
MS/TP, network, SNVT
Standards
ANSI/ASHRAE Standard 185 ;ISO-16484-5; ISO-16484-6
IEC 61158 
ANSI/EIA 709.1; ISO/IEC 14908-1, 14908-2, 14908-3, 14908-4
Costs
Low; No charge for usage or licensing fees
Low; No charge for usage or licensing fees
High (proprietary); Limited users (exclusive to actual members;  mostly manufacturers)
Network Interfaces
Existing LANs and LANs infrastructure
Traditional serial and Ethernet protocols
U10/U20 USB Network Interface; i.LON SmartServer; i.LON 600
Testing
BACnet Testing Labs
Modbus TCP Conformance Testing Program
Products must  conform to LonWorks protocol
Advantages
- Scalability between cost, performance and system size
- Easy connection to Modicon
- Web based tool; saves time and cost
- Endorsement and adoption by nearly every major vendor in North America and many other countries
- Suitable for small/medium volumes of data (≤255 bytes)
- Numerous developers of LonWorks products in the market
- Robust internetworking including multiple LAN types and dial-up
- Data transfer designed for industrial applications
- Less Architecture at device level
- Unrestricted growth and the ability to add new innovations and new features anytime
- Openly published and royalty-free


- Easy to deploy and maintain


- Moves raw bits or words without placing restrictions on vendors

Disadvantages
- Limited the number of field devices that can connect to a master station except Ethernet TCP/IP
- Limited the number of data types; Large binary objects are not supported.
- Outdated
- MT/TP-Wire Length
- No standard method for a node to find the description of a data object, i.e. finding a register value represents a temperature between 30 and 175.
- Controlled devices & variables are connected to a separate control device. (Not recommended due to network interruptions producing system failures)
- Ethernet-Infrastructure
- No security against unauthorized commands or interception of data
- Extensions are allowed only through the LonMark Consortium.
- New standard has security standard but not implemented in all devices
- Transmissions must be contiguous which limits the types of remote communications devices to those that can buffer data to avoid gaps in the transmission.
- Hardware specific, and requires the Neuron chip for network movement of the protocol.

- Great amount of configuration and programming required
- Close to “plug & play” ability, yet still far from achieving interconnectivity using Microsoft Windows.

- Protocol is not common in the SIMATIC family


To determine whether a BMS protocol is open, ask the vendor two simple questions:
1.     Can your competitors exchange data with your BMS?
2.     Is the system’s protocol published in such a way that it’s easily accessible to everyone (including competitors)?



Even the ASHRAE BACNet committee has convened a working group to define use of XML with BACnet systems. The group is also working to define web services that will enable data exchange between building automation and control systems and various enterprise management systems.

Use these criteria when you’re choosing devices and BMS:
1.     For devices such as RTUs and refrigeration controllers, look for ones that use open protocols such as BACnet or Modbus.
2.     Make sure these devices give you both “read” and “write” capabilities so you can change set points.
3.     For easy enterprise access, choose a BMS with web services and XML capabilities.
4.     Make sure the web services of the BMS allow both read and write capabilities.
5.     Be sure the BMS supplier provides the XML dictionary and definitions of web services to anyone, including competitors.