Saturday, August 24, 2019

SSA Integrate - Fire alarms and BAS

SSA Integrate - Fire alarms and BAS

The integration of Building Automation System and fire alarm systems can result in overall reduction in equipment, installation, and maintenance costs while still maintaining the level of safety required for these systems to operate. 

With the advent of smart building technology, heating, cooling, electrical, lighting, security, and other systems need monitoring and intercommunication for optimized efficiency and operation. With sophistication comes the need for a building automation system (BAS) to allow for nearly seamless operation of these various interrelated equipment.
When the fire alarm system takes control of equipment that is not a listed component of the fire alarm control unit, the fire alarm system must either override the natural operating mode of the building equipment or pass off that command via a simple switch or data communications to the building mechanical systems. Likewise, each manufacturer’s BAS has its own protocol for monitoring conditions and communicating operational commands to maintain the proper building environment and efficiency. There are also standard open communication protocols such as LonTalk and BACnet that can be used to communicate with a multitude of equipment from various manufacturers in order to achieve an integrated building system. 
The communication protocol for a fire alarm control unit to communicate to and from its indicating (input), initiating (output), and sometimes notification appliances is typically an analog or digital communications signal carried over what is referred to as a signaling line circuit (SLC). Because communications signals are typically proprietary protocol, each SLC is dedicated to a specific manufacturer’s equipment and cannot include connection of incompatible devices that use a different signal protocol.
Therefore, in order to integrate system alarm and control functions with the BAS in a manner other than relay logic, fire alarm system manufacturers had to also design and support the open communication protocols used for building automation, in a manner that would not compromise the integrity or the operation of the fire alarm system. This process of sharing information between both fire alarm and BAS came to be known as bridging, or open gateway processing. Because of the strict code and listing requirements of fire alarm systems, much of this communication has been primarily limited to one-way communication. However, some manufacturers of both fire alarm and BAS do produce equipment such as gateways that are listed for bi-directional communication with their equipment. 

Make a case of a building with separate building automation and fire alarm systems: When the building engineer receives a call from an occupant complaining about increased temperature or whistling air within the ductwork and finds that the fan is shut down or a damper is closed, the building engineer is more apt to call a controls contractor to investigate the problem before he calls their fire alarm service provider. Should the problem be related to an override of controls by the fire alarm systems, not only does the building engineer have to wait for the controls contractor to diagnose the problem, he also has to call the fire alarm contractor to come out and fix the problem. This process can take time to correct; meanwhile, building occupants are uncomfortable and inconvenienced.
Sometimes this can even lead to finger-pointing between the two service providers as to whose problem it really is. In this scenario, the fire alarm control of a fan or a damper is required to be ahead of the hand-off-auto switch for the power to the equipment so the inadvertent shutdown of the equipment does not inhibit the operation of the fire alarm feature. A failure of the fire alarm system control relay could shut down the fan or close the damper without an alarm being present on the fire alarm system or fault condition occurring on the fire alarm control unit. 

Because many components that affect air and smoke movement within a building are shared between HVAC and fire alarm systems, let’s take a step backward in the evolution of the building process. When building systems are being commissioned for proper operation by either an authority having jurisdiction (AHJ) or an independent third-party group, coordination must occur between multiple trades. At this point in the construction process, each trade is independently looking to complete its own scope of work and more often than not is under pressure to finish the specific scope in a designated timeframe. Sometimes this leaves a disconnect between the fire alarm and mechanical trades that results in disruption during start-up and commissioning. 

The integrated system approach allows for those individuals responsible for controlling air movement to be focused on proofing and balancing the mechanical system, while the fire alarm contractors focus on the detection and annunciation of the alarm events. Much in the same manner as referenced in the previous example, the problems can get resolved more expeditiously and the systems can be brought on-line. 

If we focus on the installation of a building management system (BMS) and a fire alarm system, we see many similarities. Each of these control systems is classified as low-voltage systems that communicate to their respected devices through an analog or digital signal. Their wiring methods and materials are similar, and often their respective equipment is located in the same general area and is performing the same basic functions with one significant difference: the fire alarm system uses individual point addressable monitor and control modules while the BAS uses digital input/output driver assemblies that communicate with different protocols. 
Why is this important? Because the BAS still requires individual pairs of conductors to each point being controlled or monitored by the digital input/output module, resulting in more wire being needed and longer installation time.

When considering SSA system integration, the ability of the BAS to control a smoke control system operation falls under the auspice of the jurisdiction’s building code, often based on the model building codes. The IBC has been adopted by a large portion of the United States and is used in this article as an example. IBC Section 909 covers smoke control systems, the procedures for determining system parameters, the acceptable methods that may be used to accomplish smoke control, and the requirements to document the system’s actual performance. It recognizes that the smoke control system is a life safety system and must maintain the same high level of reliability required for any type of fire protection or fire alarm system.

Section 909 requires smoke control systems to be initiated by sprinkler system or smoke detection system operation, depending on the type of system being designed. It also requires systems providing control input or output to the mechanical smoke control systems to comply with Section 907 (Fire Alarm and Detection Systems) and NFPA 72: National Fire Alarm and Signaling Code, and states that such systems must be equipped with a control unit that complies with UL 864 and has to be listed as smoke control equipment.

Using a fire/smoke damper that is part of an engineered smoke control system complying with International Building Code Section 909 as an example, at each damper location we have a smoke detector for detection of smoke, an actuator that controls the opening and closing of the damper, and an end switch to provide positive confirmation of the damper open and closed position. Because the fire alarm system already needs to have circuitry to this location for individual smoke or duct smoke detectors, that same pair of wires can be used to monitor the open and closed position of the damper, essentially eliminating two pairs of wires back to the BAS controller. The position status signals of the damper can then be transmitted from the fire alarm system, through the gateway, and into the BAS along with the active alarm point information. This leaves the wiring to the actuator as the only BAS wiring needed at the damper location.
As another example, let’s use a stairway pressurization fan that is being controlled by a variable frequency drive (VFD). Typically, a VFD would be connected to the BAS via a digital signal while the fire alarm system would provide override of the VFD using dry contacts to stop it or put it into a smoke mode condition. Allowing the BAS to perform all of the control functions permits the adjustment of the fan speed through the BAS to regulate for atmospheric conditions by employing other equipment connected to the BAS, such a digital differential pressure sensors. Using the BAS solely for control eliminates any connection to the fire alarm system, with the activation commands being sent through the gateway.

Taking advantage of the aforementioned efficiencies gained by integrating the BAS with the fire alarm system requires planning in the design process. This planning process is the same whether it is a design build or a design assist type of project delivery. The building owner and operator must be involved in the process of establishing the design criteria or at the least have influence over it. In a typical design build or design assist process, the integration of these two systems is an afterthought and often never considered. The end user must be made to understand that the efficiencies gained by integration will pay dividends long into the lifecycle of the building.

Integrated systems require enough time to test and to verify that the system interoperability is functioning properly. It is important that the engineer as well as the installing contractor and the equipment vendors understand the impact of these requirements on providing an approved and code compliant installation. 
Due to the complexity of these systems and the required integration, testing must confirm that the functions and sequences work correctly under both automatic and manual modes.

The inspection and testing of integrated systems is usually exasperating and time-consuming, and often requires multiple rounds of retesting before all the deficiencies are corrected. This is often caused due to all of these different systems being completed late in the schedule and not enough time to “get the kinks out” prior to final testing. Anything that can expedite the commissioning process is beneficial to the overall project. 

One of the advantages of using the BAS as an integrated part of the smoke control system is the system’s ability to modify operating conditions to accommodate actual ambient conditions through the use of VFDs. The design of smoke control systems is based on many variable conditions, including temperature, wind conditions, and the quality or “tightness” of the construction. These conditions tend to make testing and adjusting of the smoke control system difficult at best.

Integrating BAS can help minimize test stress by adjusting the fan speed of individual fans through programming. In a situation of excessive stair pressurization, the individual fan can be adjusted to limit its airflow to the stair, resulting in a lower level of pressure affecting door opening forces. Similarly, for individual zone smoke control system performance, the fan speed can be adjusted on a zone-by-zone basis, based on the fire alarm signal received by the BAS. 

The downside to this operation is that the BAS controls are typically located remotely to the fire alarm control panel and the firefighters’ smoke control panel, both of which normally reside in a fire command room. BAS controls and system components are usually located for the convenience of the building’s staff and HVAC equipment. Under test conditions, additional personnel may be required to monitor the BAS controls to make any required modifications. 

While modifying fan output for each smoke zone condition is a more expedient method to obtain approval, it also provides future opportunities to inappropriately change the settings, possibly making the system ineffective. Care must be taken to limit access to this programming and provide logging procedures to document when and why changes are made.
Take a note: Fire condition is determined by the Fire Alarm Control Panel. AHU will automatically shutdowns the whole system with associated interlocks.

Question: How can the reliability of the fire alarm system be maintained while mixing data with other non-emergency inputs?
Answer: In reality the fire alarm system reliability is unaffected by other integrated systems when using the BACnet protocol due to the required use of the gateway interface. The gateway keeps the other signals on the network form affecting the fire alarm system.

Question: Building automation systems are more and more residing on an owner's IT network. If a BACnet gateway is used to interface to the fire alarm system, instead of hardwired connections, this device would reside on the owner's network which is likely not UL listed. Have you come across this concern?
Answer: The BACnet gateway itself is required to be listed, but not the system. So the fire alarm system devices or zones would be connected to the listed gateway and then the other side of the gateway would be connected to the network allowing the objects to be transmitted to the BAS, for example. Once again we are still required to use the listed gateway as the interface but the balance of the non-fire alarm system equipment does not need to be listed for fire alarm use. Having said that there are changes proposed to NFPA 72-2019 that would allow direct connection to the Ethernet or a network under certain conditions. These proposed changes have not yet been officially adopted.

Question: Do you recommend integrating the building fire alarm system and the BAS in an office building that undergo tenant fit-outs on a continuous basis?
Answer: With any system design in any building or occupancy planning is imperative. Knowing beforehand that the occupancy is to be offices and knowing that tenant fit-out occur on a regular basis, it is incumbent on the original system designer to include system changes and expansion in his or her design. Just because frequent changes to a system are expected does not preclude integrating all of the systems. It does require more coordination and provided that happens the systems should remain reliable.

Question: Does OEO override designated and alternate recall operation?
Answer: No, just the opposite. All recall features (elevator lobby smoke detectors for example) would input to the OEO controller and it would relinquish OEO or those floors in recall.

Question: How would elevator shunt trip for a sprinkled hoistway or elevator equipment room operation work into the OEO sequence of operation?
Answer: As stated previously, when these types of operations occur during or prior to OEO, these operations would take priority over the OEO and all OEO for the affected elevators would cease and all signs and voice messages would revert to “Do Not Use The Elevators, Use The Stairs” operation. 

Question: How would the use of BACnet interface to emergency control systems, requiring supervision of control wiring, address this code requirement?

Answer: NFPA 72-2019 (and previous editions) require supervision to within 3 ft of the controlling device or no supervision if the device operation is fail-safe, meaning if the connection to the device is severed, the emergency device operates as required. The gateway could be determined as the connection to the controlling device and as long as that was within 3 ft of the controller it would be considered code-compliant. This is unlikely to happen and other design considerations will need to be considered to ensure that the performance of the emergency control system is code compliant. Given the many types of configurations, there can be no one definitive answer to the problem until the actual field condition is evaluated.

24 comments:

jazeera khan said...

Wireless Access Points

Wireless Survey

   CISCO Video Conferencing

 CISCO WebEx
 Aruba Wireless Access Points

Meraki Wireless Access Points

Wireless Access Points services in bangalore

Praveen Kumar Pundhir said...

nice artical sir...

Kuldeep Singh - Bihar said...

Humko malum hai k
१- CLASS A - ठोश अग्नी ( SOLID FIRE ) = ऐसी अग्नी जिसमे लकड़ी , कागज , ओर वस्त्रो जैसे ठोश पदार्थ सामिल हो .
२- CLASS B - तरल अग्नी ( LIQUID FIRE ) = ऐसी अग्नी जिसमे पेट्रोल, डीजल, या तेल जैसी ज्वलनशील तरल पदार्थ सामिल हो .
३- CLASS C - गसिऔस अग्नी ( GASEOUS FIRE ) = ऐसी अग्नी जिसमे गैस सामिल हो
४- CLASS D - धातु अग्नी ( METAL FIRE ) = ऐसी अग्नी जिसमे मग्निसियम, सोडियम जैसे धातु सामिल हो.
५- CLASS E - विद्युतीय अग्नी ( ELECTRICAL FIRE ) = ऐसी अग्नी जिसमे विधुत उपकरण सामिल हो.

No Name said...

Hey Guys !

USA Fresh & Verified SSN Leads along with DL Number, AVAILABLE with 99.9% connectivity
All Leads have genuine & valid information.

**HEADERS IN LEADS**
First Name | Last Name | SSN | Dob | DL Number | Address | City | State | Zip | Phone Number | Account Number | Bank Name | Employee Details | IP Address

*Price for SSN lead $2
*You can ask for sample before any deal
*If anyone buy in bulk, we can negotiate
*Sampling is just for serious buyers

==>ACTIVE, FRESH CC & CVV FULLZ AVAILABLE<==
->$5 PER EACH

->Hope for the long term deal
->Interested buyers will be welcome

**Contact 24/7**
Whatsapp > +923172721122
Email > leads.sellers1212@gmail.com
Telegram > @leadsupplier
ICQ > 752822040

vishal said...

Thanks For sharing very helpful information
Fire Alarm System

Exotic Media said...

Fire system is more than necessity as the population is booming as fire security has also been taken very serious by the government
fire alarm system company

fire hydrant manufacturers in india

fire protection system companies

Ganesh said...

Nice Blog....Fire Alarm System in Chennai
PLC Automation Companies in Chennai
Control Panel Manufacturers in Chennai

Nilesh Pawar said...

Great post. I was once checking constantly this weblog and I'm impressed! Extremely useful information specially the closing part. I maintain such information much. I was once seeking this specific information for a very long time. Many thanks and best of luck.
fire extinguisher manufacturer in Maharashtra

SAS Systems said...

SAS Systems Engineering is on-hand for all your fire protection, security and communications, building management and automation system needs. Backed by a number of years in this industry, you can rest assured that our highly skilled team of engineers provides high levels of service including fire protection systems, fire alarms, security systems, CCTV.Access Control, intrusion detection computerized monitoring, motion detection, perimeter protection, Closed Circuit Televisions (CCTV), burglar-alarm systems and fire alarms service in Saudi Arabia.

Fire Hydrant system said...

Hi,
This blog information is good. this information is really very good. Thanks for sharing this valuable information with us.
Fire alarm system Manufacturer
Fire alarm system Supplier

Fire Hydrant System, Fire Sprinkler System, Fire Alarm System, Fire Extinguisher system, Foam Flooding System, Medium Velocity Water Spray System, High Velocity Water Spray System, Building Management System, Security CCTV System, Access Control System, Public Address System, Kitchen Fire Suppression System, Electrical Panel Fire Suppression System, Flammable and Toxic Gas Detection System, Gas Based Fire Suppression System, Vehicle Fire Suppression System, Fire Safety Audit Services, Design and Detail Engineering Fire Protection System, Spark Detection and Suppression System, manufacturer, supplier

Petronext International said...

This is a fantastic post. I found this blog to be quite interesting and informative. Continue to share more insightful posts. Also check out Fire and Safety Companies in Abu Dhabi.

Nilesh Pawar Digital Marketing Expert said...

Thanks for sharing such beautiful information with us. I hope you will share some more information about Industrial Fire Protection Equipment for sale in Maharashtra.Please keep sharing.

Dnieper Fire & Safety said...

Many Efforts to explain the crucial information
Fire Safety Equipment Suppliers UAE
fire alarm system suppliers in uae

Anonymous said...

Our water level controllers in chennai, Chennai form here we are supplying all of Coimbatore, Madurai, Trichy, Tirunelveli, and Tamil Nadu as well as all over India. Our branch offices are OMR, Velachery, Anna Nagar

Fused Electric said...

Nice! your blog is very informative and great. If your are looking for these best Fire Alarm Installation Certificate services. Our company provides the best services in United Kingdom.

KTRONICS said...

KTronics controllers are specially designed for water level control and level indication purposes. It is developed with fit for all motors simple operations.

LeBastiano said...

Wow! Awesome article!

Make money review

KTRONICS said...

Manufactures of Automatic water level controller and Indicator in Chennai and Tamilnadu, wireless water tank level indicator and wireless water level controller in Chennai, OMR, Anna Nagar, Velachery.

navya sree said...

This post is extremely radiant. I extremely like this post. It is outstanding among other posts that I’ve read in quite a while. Much obliged for this better than the average post. I truly value it! fire control station on ship

navya sree said...

This post is extremely radiant. I extremely like this post. It is outstanding among other posts that I’ve read in quite a while. Much obliged for this better than the average post. I truly value it! smoke damper

Dubai Commercial Business Directory said...

Get Security Control Equipment Systems Suppliers In UAE supplying quality items includes metal detectors, alarm systems, razor wire, etc at affordable rates.
Visit , https://www.atninfo.com/uae/all/security-control-equipment-systems-1330

Dubai Commercial Business Directory said...

Get Security Control Equipment Systems Suppliers In UAE supplying quality items includes metal detectors, alarm systems, razor wire, etc at affordable rates
Visit , https://www.atninfo.com/uae/all/security-control-equipment-systems-1330

FMC Fire Systems said...

Critical combo: Fire alarms and BAS enhance safety and efficiency! FMC Fire Systems

AnnuAnusha said...

Firetech fire monitors are robust products designed with advanced technology.
foam generator